Installation And
Operation Manual
SUPERCHANGER
®
PLATE & FRAME HEAT EXCHANGER
www.tranter.com
Seitenansicht 0
1 2 3 4 5 6 ... 47 48

Inhaltsverzeichnis

Seite 1 - Operation Manual

Installation And Operation ManualSUPERCHANGER®PLATE & FRAME HEAT EXCHANGERwww.tranter.com

Seite 2 - TABLE OF CONTENTS

10Plate Pack Widths“A” Dimension for standard thickness materialsCalculating the “A” dimension (Plate Pack Width in Inches) for various SUPERCHANGER M

Seite 3 - EQUIPMENT LOG SHEET

11Plate DesignationsSUPERCHANGER units are designed so that a fl uid which enters the “A” plate circuit (nozzles S1, S2, M1 or M2) always fl ows

Seite 4 - AND CONSTRUCTION

12Element Composition DiagramFigure 13 shows an “S” frame (stationary member), “E” frame (moveable member) and plates of the plate heat exchan

Seite 5 - Plate Details

13Plate Hole Designation for UX, SX, GC and GF SeriesAs shown in Figure 14, the pierced holes at the corners of the plate are designated as: 1 for upp

Seite 6 - GXD-042-H-7-UP-102

14*No number indicates that fl uid passes through all four holes in the plate. Flow Down Plate Flow Up PlateFigure 17 Element composition diagram.

Seite 7 - P 0X X XX

15Figure 18 Flow arrangement.A sideB sideQ1/2Q1Q2Q1Q2Q2/3*No number indicates that fl uid passes through all four holes in the plate.DrainsT h e r e

Seite 8 - Frame Pressure Ratings

16Figure 20 Five-pass unit with 2 passes that are not drainable.Figure 21 Five-pass with pass 3 and 4 as drainable. (Plates 8 and 9 have small drain

Seite 9 - Condensed Unit Specifications

17Connecting “C” FramesSUPERCHANGER units can be partitioned into multiple sections by employing the required number of connecting “C” frames wh

Seite 10 - Plate Pack Widths

18PLATE STYLESUnlike all other SUPERCHANGER models, the GX series of plates is based on a diagonal fl ow pattern. On a typical one-by-one pass unit, n

Seite 11 - Plate Designations

19DrawingsThe bottom left hand corner of each GF and GX unit drawing has a plate specifi cation chart and plate arrangement/assembly listing to assist

Seite 12 - Drawings

2TABLE OF CONTENTSEQUIPMENT LOG SHEET 3IDENTIFYING YOUR SUPERCHANGER® UNIT 3PLATE DESCRIPTIONAND CONSTRUCTION 4Plate Details 5Unit Part Numbers 6

Seite 13 - GC and GF Series

20Four-Plate SequenceIn some instances, the arrangement in a GX model will follow a repeating four-plate sequence. An example is shown below:Figure 3

Seite 14 - Pass Arrangement

21GASKET DATAGasket Material Max. Temp. (oF)Color CodeEPDM (Full FDA Approved) 300 1 Grey + 1 RedEPDM (Industrial Grade) 338 1 GreyEPDM (Partial FDA A

Seite 15

22Gaskets—GluelessSUPERLOCK®Functionally, Tranter’s patented SUPERLOCK® glueless gaskets perform in the same manner as glued gaskets (see Figures 30,

Seite 16 - Figure 22

23Gasket Storage ProceduresWhen SUPERCHANGER heat exchanger plate gaskets are maintained as spare parts, it is important that certain storage

Seite 17 - Connecting “C” Frames

24Mixed Gasket MaterialsMost SUPERCHANGER units are equipped with gaskets made of one material. However, there are two conditions that dictate the us

Seite 18 - PLATE STYLES

25PLATE NO. GASKET PLATE GLUING HANGING1 NBR (S) H0230 RC START B2, 4, 6, 8, 10 NBR (S) H1234 LG E3, 5, 7, 9, 11 NBR (S) H1234 RC B12, 14, 16, 18 NBR

Seite 19

26GX Gluing CodesRight CRCLeft GLGRight LRLLeft SLSLeft CLCRight GRGLeft LLLRight SRSLeft BLBRight ERELeft KLKRight RRRDiagonal Flow Plates:Parallel F

Seite 20 - Multi-Pass Units

27GX Start and End Plate ExplanationsFigure 38* These gaskets are half thickness and may be pieced together in various ways depending upon specifi c mo

Seite 21 - Gaskets—Glued

28INSTALLATIONUnpackingSUPERCHANGER units (with optional shroud) are bolted to and shipped assembled on a skid. Other optional items, if suppl

Seite 22 - Gaskets—Glueless

29Tightening the Plate PackThe plate pack tightening length (distance between the facing surfaces of the “S” and “E” frames) is given on the

Seite 23 - Gasket Storage Procedures

3R�IDENTIFYING YOUR SUPERCHANGER® UNITFigure 1A data plate like the one shown on the picture above is fixed to the stationary frame of the unit and pr

Seite 24 - Mixed Gasket Materials

30Tightening SequencesSTART-UP PROCEDURESPrecautions Prior to Start-Up1. If there is particulate matter in the process streams, contact your Tranter

Seite 25

31SERVICING Shutting Down the Unit1. Gradually decrease the pressure of both fl uids simultaneously until all pressure is relieved.2. Never open a

Seite 26 - GX Gluing Codes

32Replacing PlatesA faulty plate can easily be removed and replaced by a spare plate. Check that the new plate has the holes and gaskets arranged in

Seite 27 - Figure 38

33Installing Continuously Glued Gaskets1. Make sure the gasket groove area is clean and dry prior to regasketing.2. Apply a uniform layer of ad

Seite 28 - Recommended Procedures

34Installing Spot-Glued GasketsSpot gluing of Elastomeric gaskets is covered under Tranter’s U.S. Patent #5070939.In the following procedure, after th

Seite 29 - Tightening the Plate Pack

351. Position the gasket on the plate making sure that the recess in the gasket at the bleed passage location is up. When the proper side is u

Seite 30 - Precautions Prior to Start-Up

36Installing Clip-On GasketsThere is one kind of channel arrangement. The fi rst, uneven and last channel will always be S2/S4. The even channels will

Seite 31 - Removal of Plates

37Steps for Manual Cleaning of Plates1. Open the unit in accordance with disassembly procedures on page 31.2. Clean each plate separately. Dependin

Seite 32 - Replacing Gaskets

38Plate Cleaning Tips1. Do not use hydrochloric acids, or water containing in excess of 300 ppm chlorides, with stainless steel.2. Do not use pho

Seite 33

39Often, when fibers or large particulates are present, back flush-ing of the unit proves to be very beneficial. This is accom-plished by ei

Seite 34 - Installing Spot-Glued Gaskets

4PLATE DESCRIPTIONAND CONSTRUCTIONSUPERCHANGER plate corrugations are available in four patterns. Depending on the applications, the GF,

Seite 35 - Snap-In Gaskets

40TROUBLESHOOTING Figure 49Troubleshooting sources of leaks.213

Seite 36 - Installing Clip-On Gaskets

41Leakage Between the Plate Pack and the Frame(See Figure 49, Item 1) Leakage Between the Nozzle and the End Frame(See Figure 49, Item 2)ACBFigure 50T

Seite 37 - CLEANING

42Leakage Between the Plates to the Outside of the Unit(See Figure 49, Item 3)Mixing of Fluids PROCEDURES AND OBSERVATIONS SOLUTIONS1. Mark the a

Seite 38 - Cleaning-In-Place (CIP)

43Increase in Pressure Drop or a Reduction in Temperature ReadingHow to Find a Defective Plate With Through Holes Severe corrosion may cause defec

Seite 39 - Back Flushing and Strainers

44When a SUPERCHANGER plate and frame heat exchanger is to be placed in storage for six months or longer, the procedures listed below must be followed

Seite 40 - TROUBLESHOOTING

45MISCELLANEOUS INSTRUCTIONSGeneral MaintenanceIt is recommended that tightening bolts and tightening nuts be lubricated periodically in order that th

Seite 41

46SUPERCHANGER units are plate and frame type heat exchangers consisting of corrugated heat transfer plates, frames, nozzles and tightening bol

Seite 43

www.tranter.comSC-IOM-11-0107 650531 © 2007 Tranter, Inc.At the forefront of heat exchanger technology for more than 70 yearsTranter top quality

Seite 44 - STORAGE PROCEDURES

5Plate DetailsFigure 4Typical UX, SX or GC Series (herringbone) plate with gasket and hanger. Note that the chevron angle for the herringbone plate c

Seite 45

6Figure 8 displays a typical SUPERCHANGER unit part number. The first entry represents the plate style (two-letter code) and flow, such as:GX Gasketed

Seite 46 - Authorized Service Centers

7Plate Material and Date of Manufacture DataFigure 9General locations of code stamping for various plate models.All plates are stamped with identifcat

Seite 47

8Old Name New NameGlued Gasket ModelsGC-12 GCD-012GC-30 GCD-030GC-48 GCD-048GC-50 GCD-050GC-26 GCP-026GC-28 GCP-028GC-51 GCP-051GC-60 GCP-060S3 GFP-03

Seite 48 - Tranter India Pvt. Ltd

9Table 2Nominal Frame Dimensions Channel Volume Between Plates (gal)Model Height (in.) Width (in.) Connection (in.) Max. Flow (gpm) Wide Medium Narrow