Velocity Edge GX325 Bedienungsanleitung Seite 13

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 48
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 12
13
Plate Hole Designation for UX, SX,
GC and GF Series
As shown in Figure 14, the pierced holes at the corners of the
plate are designated as: 1 for upper right, 2 for lower right, 3 for
lower left and 4 for upper left when facing the gasketed side of
the plate. Plates 1 and 2 in Figure 14 are represented as A1234
and B1234 respectively. Plates with all four holes pierced can also
be designated with a blank space or an *. Unpierced ports will
be represented as a zero (0). For example, Plate 3 is represented
by a A1004 since there are no holes at position 2 and 3. Table
8 shows A and B equivalents when an “A” plate is rotated to
become a “B” plate.
Make sure the gaskets are installed correctly in relation to the
ow directors. (See Figures 15 and 16.)
Figure 14
Hole designations.
Figure 15
Correct gasket location.
Figure 16
Incorrect gasket location.
Chevrons point
up on “A” plates
and down on
“B” plates
NOTE: Flow
directors as related
to “A” and “B
plates
Chevrons point
up on “A” plates
and down on
“B” plates
NOTE: Flow
directors as related
to “A” and “B
plates
A” Plate
“B” Plate
A” Plate “B” Plate
Porthole designations shown apply to all units purchased
after June 1, 2002. Refer to unit drawing or previous
IOM (SC-10M-9) for older UX, SX, S, GF or TW Series.
A Plate “B” Plate A Plate “B” Plate
1234 1234 0204 0204
1034 1230 0034 1200
1204 0234 1200 0034
0234 1204 0004 0200
1230 1034 1000 0030
1004 0230 0030 1000
0230 1004 0200 0004
1030 1030 0000 0000
Table 4
“A” and “B” Equivalents
Seitenansicht 12